Standard set MT310s2 for on-site meter testing
The MT310s2 is a light weight and compact Reference Meter for on-site verification and calibration of single- or three-phase meters. Test voltage and test current can be measured by the Reference Meter directly from the mains or generated and measured via an external source (optional, e.g. MT400 or MT5xx). The MT310s2 is designed for testing of one test specimen.
Configuration
- Direct current measurement up to 300 V / 12 A
- CT current measurement up to 120 A
- Overvoltage category CAT IV
- Accuracy for power/energy measurement: < ±0.1 %
- Burden measurement for instrument transformer installations
- Additional 4th voltage and current input channel
Accessories of the standard sets
- CCB120, AC current clamp 120 A
- Factory calibration for one mains frequency
- DAkkS calibration, 50 Hz or 60 Hz (optional)
- Power cord “Euro plug type C to figure-of-eight”, 2.0 m
- CAT IV quick connection cable for “voltage/rigid sleeve” for MT s2-series, 2.0 m, phase colours: red/yellow/blue/black/black-white
- CAT IV quick connection cable for “current/rigid sleeve” for MT s2-series, 2.5 m, phase colours: red/yellow/blue
- Accessories bag with connection adapters
- TK326, scanning head with holding device and connection cable for scanning head input (SC)
- Transport case for MT3x0s2, standard
- Complete documentations as pdf files on USB flash drive
Further information about the MT310s2
Read the latest post about the interference resistance of the MT310s2 up to 150 kHz.